    Brand Name : Topband
    Model Number : TB4860F-T110D
    Certification : MSDS
    Price : Negotiable
    Payment Terms : L/C, T/T
    Supply Ability : 450Mwh/year
    Delivery Time : 2~4weeks for samples; 4~6weeks for mass production
    • Product Details
    • Company Profile

    4U LiFePO4 Telecom Batteries 48V60Ah Long Lifecycle TB4860F-T110D

    4U LiFePO4 Telecom Battery 48V60Ah Long Lifecycle TB4860F-T110D


    1. General Information

    This specification defines the performance of rechargeable LiFePO4 battery pack TB4860F -T110D manufactured by TOPBAND NEW ENERGY CO.,LTD, describes the type, performance, technical characteristics, warning and caution of the battery pack.

    2. Battery Specification(@ 25±5℃)

    NOItemsCharacteristics
    2.1Normal capacity60Ah
    2.2Nominal energy3.072KWh (16S) 2.88 KWh(15S)
    2.3Nominal voltage51.2V (16S) 48V (15S)
    2.4Internal resistance≤50mΩ @1kHz AC
    2.5Normal charge voltage58.4±0.3V 54.7±0.3V(15S)
    2.6Float charge voltage(for Standby use)55.2±0.3V 51.7±0.3V(15S)
    2.7Allowed MAX charge current50A
    2.8Recommended charge current≤25A
    2.9Allowed MAX discharge current50A
    2.10End of discharge voltage40.0V 37.5V(15S)
    2.11DimensionLength 482±2 mm
    height 173±2 mm
    Depth 445±2 mm
    2.12WeightApprox. 38kg
    2.13Operation temperatureCharge0~45℃
    Discharge-20~60℃
    2.14Self-discharge rateResidual capacity≤2%/Month; ≤10%/ year
    Recover capacity≤1%/Month; ≤6%/ year
    2.15Storage environment≤1month-20~+35℃, 45~75%RH
    ≥3month-10~+35℃, 45~75%RH
    Recommend environment15~30℃, 45~75%RH

    3. Electrical Characteristics & Test Condition

    Testing Conditions: Ambient Temperature: 25±5℃; Huminity:45%~75%.

    Normal charge:Charge battery under CC(0.33C)/CV(58.4V) mode until over charge protection or the charge current reduce to 0.05C, and then rest for 1h.


    NOItemsCriterionCondition
    3.1Normal Capacity60AhAfter Normal charge, discharge @0.33C current to the end of discharge voltage.
    3.2Internal Impedance≤50mΩ@50% SOC @1kHz AC internal resistance test instrument.
    3.3Short circuit protectionAuto cutoff load when short circuitConnect the positive and negative of this battery pack through a lead with 0.1Ω resistance.
    3.4Cycle life @DOD100%≥2000 cyclesAfter Normal charge,discharge @0.33C current to the end of discharge voltage. Repeat above process until discharge capacity reduce to 80% of initial value.
    3.5

    Discharge temperature

    characteristic@0.33C

    -20℃≥70%

    Capacity @specified temperature

    4U LiFePO4 Telecom Batteries 48V60Ah Long Lifecycle TB4860F-T110DCapacity @ 25℃


    -0℃≥80%
    25℃≥100%
    55℃≥95%
    3.6Capacity retention rate

    remain capacity

    ≥96%

    After normal charge, store the battery @25±5℃ for 28days, then discharge capacity @0.33C,the retention capacity accord with criterion.
    4. Circuit Protection

    The batteries are supplied with a LiFePO4 Battery Management System (BMS)that can monitor and optimized each single prismatic cell during charge & discharge, to protect the battery pack overcharge, over discharge, short circuit. Overall, the BMS helps to ensure safe and accurate running.


    NoItemContentCriterion
    4.1Over chargeOver-charge warning for each cell3.60±0.03V
    Over-charge protection for each cell3.70±0.03V
    Over-charge release for each cell3.38±0.05V
    Over-charge release methodUnder the release voltage
    4.2Over dischargeOver-discharge warning for each cell2.80±0.05V
    Over-discharge protection each cell2.50±0.05V
    Over-discharge release for each cell2.90±0.10V
    Over-discharge release methodCharging
    4.3Over currentCharge over current warning55±3A
    Charge over current protection60A±3A
    Charge over current releaseDischarge or auto release after 1min
    Discharge over current warning55±3A
    Discharge over current protection60A±3A
    Discharge over current releaseCharge or auto release after 1min
    Short circuit protectionAvailable
    4.4TemperatureCharge over temperature protectionProtect@55±3℃; Release@50±3℃;
    Charge under temperature protectionProtect@0±3℃; Release@5±3℃
    Discharge over temperature protectionProtect@65±3℃; Release@60±3℃;
    Discharge under temperature protectionProtect@-20±3℃; Release@-15±3℃;

    5. User guide

    5.1 TB48XXF-T110X Operation principle and Wiring hint

    Input 220Vac, after rectification power module, output 48V. When the power grid normal, the battery will supply power according to system requirement, and to be charged at same time; when power off, the battery will supply energy, to make sure the DC power system working normally, to realize uninterruptible power supply. The power supply has second disconnection function, when the battery voltage is low, the battery output would be cut off to protect battery life.


    5.2 Operation panel direction(TB48XX Series general reference)

    Reset RS485 RS232 Dial switch RUN LED alarm LED SOC LED


    5.3 sleep mode

    The system would go into low-consumption mode in any of the following conditions:

    1. Single module or the whole system over discharge protection not recovered in 30s
    2. Press the keys for 3s
    1. The minimum single voltage lower than sleep voltage, and the lasting time reach sleep delay time( no communication, no protection, no balance, no current at same time).
    2. Standby more than 24h( no communication, no charge or discharge, no AC input).
    3. Force shutdown through upper-computer software.

    Before sleep mode, please make sure there is no input voltage, otherwise it can no go to sleep mode.

    5.4 wake up

    1. Connect to charger, and the charger output is more than 48V.
    2. Press the keys for 3s;
    3. Connect to communication cable, open upper computer software( if it goes to sleep mode due to over discharge protection, this method would not wake up the circuit board).

    Remark: single model or the whole system goes to low-consumption mode after over discharge protection, it would be wake-up every 4hs, to open discharge MOS. If it can be charged, it would exit sleep mode and start normal charge; if it fails to be charged after 10times of wake-up automatically, there would be no automatic wake-up.


    5.5 Installation drawing

    Case dimension: 482(Width) * 570(Depth) * 176(height) mm;

    Handle Depth:35mm; weight:Approx.59kg.

    Quality 4U LiFePO4 Telecom Batteries 48V60Ah Long Lifecycle TB4860F-T110D for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Shenzhen Topband Battery Co., Ltd
    *Subject:
    *Message:
    Characters Remaining: (0/3000)